| Range of product |
Altivar 71
|
| Product or component type |
Variable speed drive
|
| Product specific application |
Complex, high-power machines
|
| Component name |
ATV71
|
| Motor power kW |
132 kW, 3 phases at 380...480 V
|
| Motor power hp |
200 hp, 3 phases at 380...480 V
|
| Maximum motor cable length |
100 m shielded cable 200 m unshielded cable
|
| Power supply voltage |
380...480 V - 15...10 %
|
| Network number of phases |
3 phases
|
| Line current |
192 A for 480 V 3 phases 132 kW / 200 hp 239 A for 380 V 3 phases 132 kW / 200 hp
|
| EMC filter |
Integrated
|
| Assembly style |
With heat sink
|
| Variant |
Reinforced version
|
| Apparent power |
157.3 kVA at 380 V 3 phases 132 kW / 200 hp
|
| Prospective line Isc |
35 kA for 3 phases
|
| Nominal output current |
259 A at 2.5 kHz 380 V 3 phases 132 kW / 200 hp 259 A at 2.5 kHz 460 V 3 phases 132 kW / 200 hp
|
| Maximum transient current |
388 A for 60 s 3 phases 132 kW / 200 hp 427 A for 2 s 3 phases 132 kW / 200 hp
|
| Output frequency |
0.1…500 Hz
|
| Nominal switching frequency |
2.5 kHz
|
| Switching frequency |
2.5...8 kHz adjustable 2.5...8 kHz with derating factor
|
| Asynchronous motor control profile |
Voltage/frequency ratio (2 or 5 points) Sensorless flux vector control (SFVC) (voltage or current vector) Flux vector control (FVC) with sensor (current vector) ENA (Energy adaptation) system for unbalanced loads
|
| Type of polarization |
No impedance for Modbus |