| Local display |
With
|
| Number or control scheme lines |
0…240 with ladder programming 0…500 with FBD programming
|
| Cycle time |
6…90 ms
|
| Backup time |
10 years at 25 °C
|
| Clock drift |
12 min/year at 0…55 °C 6 s/month at 25 °C
|
| Checks |
Program memory on each power up
|
| [Us] rated supply voltage |
100...240 V AC
|
| Supply voltage limits |
85…264 V
|
| Supply frequency |
50/60 Hz
|
| Maximum supply current |
30 mA at 240 V (without extension) 80 mA at 100 V (without extension)
|
| Power consumption in VA |
7 VA without extension
|
| Isolation voltage |
1780 V
|
| Protection type |
Against inversion of terminals (control instructions not executed)
|
| Discrete input number |
8
|
| Discrete input voltage |
100...240 V AC
|
| Discrete input current |
0.6 mA
|
| Discrete input frequency |
47...53 Hz 57...63 Hz
|
| Voltage state 1 guaranteed |
>= 79 V for discrete input
|
| Voltage state 0 guaranteed |
<= 40 V for discrete input
|
| Current state 1 guaranteed |
>= 0.17 mA (discrete input)
|
| Current state 0 guaranteed |
<= 0.5 mA (discrete input)
|
| Input impedance |
350 kOhm for discrete input
|
| Number of outputs |
4 relay
|
| Output voltage limits |
5...30 V DC (relay output) 24...250 V AC
|
| Contacts type and composition |
NO for relay output
|
| Output thermal current |
8 A for all 4 outputs for relay output
|
| Electrical durability |
AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1 DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
|
| Switching capacity in mA |
>= 10 mA at 12 V (relay output)
|
| Operating rate in Hz |
0.1 Hz (at Ie) for relay output 10 Hz (no load) for relay output
|
| Mechanical durability |
10000000 cycles for relay output
|
| [Uimp] rated impulse withstand voltage |
EN/IEC 60947-1 and EN/IEC 60664-1 4 kV
|
| Clock |
With
|
| Response time |
50 ms with ladder programming (from state 0 to state 1) for discrete input 50 ms with ladder programming (from state 1 to state 0) for discrete input 50...255 ms with FBD programming (from state 0 to state 1) for discrete input 50...255 ms with FBD programming (from state 1 to state 0) for discrete input 10 ms (from state 0 to state 1) for relay output 5 ms (from state 1 to state 0) for relay output
|
| Connections - terminals |
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
|
| Tightening torque |
0.5 N.m
|
| Overvoltage category |
III conforming to EN/IEC 60664-1
|
| Net weight |